OPEN API Reference

Assets

OPEN Asset module

Asset objects define distributed energy resources (DERs) and loads. Attributes include network location, phase connection and real and reactive output power profiles over the simulation time-series. Flexible Asset classes have an update control method, which is called by EnergySystem simulation methods with control references to update the output power profiles and state variables. The update control method also implements constraints which limit the implementation of references. OPEN includes the following Asset subclasses: NondispatchableAsset for uncontrollable loads and generation sources, StorageAsset for storage systems and BuildingAsset for buildings with flexible heating, ventilation and air conditioning (HVAC).

class System.Assets.Asset(bus_id, dt, T, phases=[0, 1, 2])

An energy resource located at a particular bus in the network

Parameters:
  • bus_id (float) – id number of the bus in the network
  • dt (float) – time interval duration
  • T (int) – number of time intervals
  • phases (list, optional, default [0,1,2]) – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
Returns:

Return type:

Asset

class System.Assets.Asset_3ph(bus_id, phases, dt, T)

An energy resource located at a particular bus in the 3 phase network

Parameters:
  • bus_id (float) – id number of the bus in the network
  • phases (list) – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
  • dt (float) – time interval duration
  • T (int) – number of time intervals
Returns:

Return type:

Asset

class System.Assets.BuildingAsset(Tmax, Tmin, Hmax, Cmax, T0, C, R, CoP_heating, CoP_cooling, Ta, bus_id, dt, T, dt_ems, T_ems)

A building asset (use for flexibility from building HVAC)

Parameters:
  • Tmax (float) – Maximum temperature inside the building (Degree C)
  • = float (Tmin) – Minimum temperature inside the building (Degree C)
  • Hmax (float) – Maximum power consumed by electrical heating (kW)
  • Cmax (float) – Maximum power consumed by electrical cooling (kW)
  • deltat (float) – Time interval after which system is allowed to change decisions (h)
  • T0 (float) – Initial temperature inside the buidling (Degree C)
  • C (float) – Thermal capacitance of building (kWh/Degree C)
  • R (float) – Thermal resistance of building to outside environment(Degree C/kW)
  • CoP_heating (float) – Coefficient of performance of the heat pump (N/A)
  • CoP_cooling (float) – Coefficient of performance of the chiller (N/A)
  • Ta (numpy.ndarray) – Ambient temperature (Degree C)
  • alpha (float) – Coefficient of previous temperature in the temperature dynamics equation (N/A)
  • beta (float) – Coefficient of power consumed to heat/cool the building in the temperature dynamics equation (Degree C/kW)
  • gamma (float) – Coefficient of ambient temperature in the temperature dynamics equation (N/A)
  • Pnet (numpy.ndarray) – Input real power (kW)
  • Qnet (numpy.ndarray) – Input reactive power (kVAR)
Returns:

Return type:

Asset

update_control(Pnet)

Update the power consumed by the HVAC at time interval t

Parameters:Pnet (numpy.ndarray) – input powers over the time series (kW)
class System.Assets.NondispatchableAsset(Pnet, Qnet, bus_id, dt, T, phases=[0, 1, 2], Pnet_pred=None, Qnet_pred=None)

A 3 phase nondispatchable asset class (use for inflexible loads, PVsources etc)

Parameters:
  • Pnet (float) – uncontrolled real input powers over the time series
  • Qnet (float) – uncontrolled reactive input powers over the time series (kVar)
  • bus_id (float) – id number of the bus in the network
  • dt (float) – time interval duration
  • T (int) – number of time intervals
  • phases (list, optional, default [0,1,2]) – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
  • Pnet_pred (float or None) – predicted real input powers over the time series (kW)
  • Qnet_pred (float or None) – predicted reactive input powers over the time series (kVar)
Returns:

Return type:

Asset

class System.Assets.NondispatchableAsset_3ph(Pnet, Qnet, bus_id, phases, dt, T, Pnet_pred=None, Qnet_pred=None)

A 3 phase nondispatchable asset class (use for inflexible loads, PVsources etc)

Parameters:
  • Pnet (float) – uncontrolled real input powers over the time series
  • Qnet (float) – uncontrolled reactive input powers over the time series (kVar)
  • bus_id (float) – id number of the bus in the network
  • phases (list) – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
  • dt (float) – time interval duration
  • T (int) – number of time intervals
  • Pnet_pred (float) – predicted real input powers over the time series (kW)
  • Qnet_pred (float) – predicted reactive input powers over the time series (kVar)
Returns:

Return type:

Asset

class System.Assets.StorageAsset(Emax, Emin, Pmax, Pmin, E0, ET, bus_id, dt, T, dt_ems, T_ems, phases=[0, 1, 2], Pmax_abs=None, c_deg_lin=None, eff=1, eff_opt=1)

A storage asset (use for batteries, EVs etc.)

Parameters:
  • Emax (numpy.ndarray) – maximum energy levels over the time series (kWh)
  • Emin (numpy.ndarray) – minimum energy levels over the time series (kWh)
  • Pmax (numpy.ndarray) – maximum input powers over the time series (kW)
  • Pmin (numpy.ndarray) – minimum input powers over the time series (kW)
  • E0 (float) – initial energy level (kWh)
  • ET (float) – required terminal energy level (kWh)
  • bus_id (float) – id number of the bus in the network
  • dt (float) – time interval duration (s)
  • T (int) – number of time intervals
  • dt_ems (float) – time interval duration (energy management system time horizon) (s)
  • T_ems (int) – number of time intervals (energy management system time horizon)
  • phases (list, optional, default [0,1,2]) – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
  • Pmax_abs (float) – max power level (kW)
  • c_deg_lin (float) – battery degradation rate with energy throughput (£/kWh)
  • eff (float, default 1) – charging efficiency (between 0 and 1)
  • eff_opt (float, default 1) – charging efficiency to be used in optimiser (between 0 and 1).
  • Pnet (numpy.ndarray) – Input real power over the simulation time series (kW)
  • Qnet (numpy.ndarray) – Input reactive power over the simulation time series(kVAR)
Returns:

Return type:

Asset

update_control(Pnet)

Update the storage system power and energy profile

Parameters:Pnet (float) – input powers over the time series (kW)
update_control_t(Pnet_t, t)

Update the storage system power and energy at time interval t

Parameters:
  • Pnet_t (float) – input powers over the time series (kW)
  • t (int) – time interval
class System.Assets.StorageAsset_3ph(Emax, Emin, Pmax, Pmin, E0, ET, bus_id, phases, dt, T, dt_ems, T_ems, Pmax_abs=None, c_deg_lin=None, eff=1, eff_opt=1)

An 3 phase storage asset (use for batteries, EVs etc.)

Parameters:
  • Emax (numpy.ndarray) – maximum energy levels over the time series (kWh)
  • Emin (numpy.ndarray) – minimum energy levels over the time series (kWh)
  • Pmax (numpy.ndarray) – maximum input powers over the time series (kW)
  • Pmin (numpy.ndarray) – minimum input powers over the time series (kW)
  • E0 (float) – initial energy level (kWh)
  • ET (float) – required terminal energy level (kWh)
  • bus_id (float) – id number of the bus in the network
  • phases (list, optional, default [0,1,2]) – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
  • dt (float) – time interval duration (s)
  • T (int) – number of time intervals
  • dt_ems (float) – time interval duration (energy management system time horizon) (s)
  • T_ems (int) – number of time intervals (energy management system time horizon)
  • phases – [0, 1, 2] indicates 3 phase connection Wye: [0, 1] indicates an a,b connection Delta: [0] indicates a-b, [1] b-c, [2] c-a
  • Pmax_abs (float) – max power level (kW)
  • c_deg_lin (float) – battery degradation rate with energy throughput (£/kWh)
  • eff (float, default 1) – charging efficiency (between 0 and 1).
  • eff_opt (float, default 1) – charging efficiency to be used in optimiser (between 0 and 1).
Returns:

Return type:

Asset

update_control(Pnet)

Update the storage system power and energy profile

Parameters:Pnet (numpy.ndarray) – input powers over the time series (kW)
update_control_t(Pnet_t, t)

Update the storage system power and energy at time interval t

Parameters:
  • Pnet_t (numpy.ndarray) – input powers over the time series (kW)
  • t (int) – time interval

Energy System

OPEN Energy System Module.

The EnergySystem Class has two types of methods i) energy management system (EMS) methods which implement algorithms to calculate Asset control references, and ii) simulation methods which call an EMS method to obtain control references for Asset objects, update the state of Asset objects by calling their updatecontrol method and update the state of the Network by calling its power flow method. An EnergySystem has two separate time series, one for the EMS, and the other for simulation.

OPEN includes two EMS methods for controllable Asset objects: (i) one for multi-period optimisation with a simple ‘copper plate’ network model, and (ii) one for multi-period optimisation with a linear multi-phase distribution network model which includes voltage and current flow constraints.

Open has simulation methods for: (i) open-loop optimisation, where the EMS method is run ahead of operation to obtain controllable Asset references over the EMS time-series; and (ii) for MPC, where the EMS method is implemented with a receding horizon so that the flexible Asset references are updated at each step of the EMS time series.

class System.EnergySystem.EnergySystem(storage_assets, nondispatch_assets, network, market, dt, T, dt_ems, T_ems, building_assets=[])

Base Energy Sysem Class

Parameters:
  • storage_assets (list of objects) – Containing details of each storage asset
  • building_assets (list of objects) – Containsing details of each building asset
  • nondispatch_assets (list of objects) – Containsing details of each nondispatchable asset
  • network (object) – Object containing information about the network
  • market (object) – Object containing information about the market
  • dt_ems (float) – EMS time interval duration (hours)
  • T_ems (int) – Number of EMS time intervals
  • dt (float) – time interval duration (hours)
  • T (int) – number of time intervals
Returns:

Return type:

EnergySystem

EMS_3ph_linear_t0(t0, i_unconstrained_lines=[], v_unconstrained_buses=[])

Energy management system optimization assuming 3 phase linear network model for Model Predictive Control interval t0

Parameters:
  • self (EnergySystem object) – Object containing information on assets, market, network and time resolution.
  • t0 (int) – Interval in Model Predictive Control. If open loop, t0 = 0
  • i_unconstrained_lines (list) – List of network lines which have unconstrained current
  • v_unconstrained_buses (list) – List of buses at which the voltage is not constrained
Returns:

Output

The following numpy.ndarrays are present depending upon asset mix:

P_ES_val : Charge/discharge power for storage assets (kW) P_import_val : Power imported from central grid (kW) P_export_val : Power exported to central grid (kW) P_demand_val : System power demand at energy management time

resolution (kW)

PF_networks_lin : Network 3ph list of objects, one for each

optimisation interval, storing the linear power flow model used to formulate netowrk constraints

Return type:

dictionary

EMS_copper_plate()

Energy management system optimization assuming all assets connected to a single node.

Parameters:self (EnergySystem object) – Object containing information on assets, market, network and time resolution.
Returns:Output
The following numpy.ndarrays are present depending upon asset mix:
P_ES_val : Charge/discharge power for storage assets (kW) P_BLDG_val :Builfing power consumption (kW) P_import_val :Power imported from central grid (kW) P_export_val :Power exported to central grid (kW) P_demand_val :System power demand at energy management time
resolution
Return type:dictionary
EMS_copper_plate_t0(t0)

Setup and run a basic energy optimisation (single copper plate network model) for MPC interval t0

EMS_copper_plate_t0_c1deg(t0)

setup and run a basic energy optimisation (single copper plate network model) for MPC interval t0

simulate_network()

Run the Energy Management System in open loop and simulate a pandapower network.

Parameters:self (EnergySystem object) – Object containing information on assets, market, network and time resolution.
Returns:Output
The following numpy.ndarrays are present depending upon asset mix:
buses_Vpu : Voltage magnitude at bus (V) buses_Vang : Voltage angle at bus (rad) buses_Pnet : Real power at bus (kW) buses_Qnet : Reactive power at bus (kVAR) Pnet_market : Real power seen by the market (kW) Qnet_market : Reactive power seen by the market (kVAR) P_ES_ems : Charge/discharge power for storage assets at energy
management time resolution (kW)
P_BLDG_ems :Builfing power consumption at energy management
time resolution (kW)
P_import_ems :Power imported from central grid at energy
management time resolution (kW)
P_export_ems :Power exported to central grid at energy
management time resolution(kW)
P_demand_ems :System power demand at energy management time
resolution (kW)
Return type:dictionary
simulate_network_3phPF(ems_type='3ph', i_unconstrained_lines=[], v_unconstrained_buses=[])

Run the Energy Management System in open loop and simulate an IEEE 13 bus network either copper plate or 3ph

Parameters:
  • self (EnergySystem object) – Object containing information on assets, market, network and time resolution.
  • ems_type (string) – Identifies whether the system is copper plate or 3ph. Default 3ph
  • i_unconstrained_lines (list) – List of network lines which have unconstrained current
  • v_unconstrained_buses (list) – List of buses at which the voltage is not constrained
Returns:

Output

PF_network_res : Network power flow results stored as a list of

objects

P_ES_ems : Charge/discharge power for storage assets at energy

management time resolution (kW)

P_import_ems :Power imported from central grid at energy

management time resolution (kW)

P_export_ems :Power exported to central grid at energy

management time resolution(kW)

P_demand_ems :System power demand at energy management time

resolution (kW)

Return type:

dictionary

simulate_network_3phPF_lean(ems_type='3ph')

run the EMS in open loop and simulate a 3-phase AC network

simulate_network_mpc_3phPF(ems_type='3ph', i_unconstrained_lines=[], v_unconstrained_buses=[])

Run the Energy Management System using Model Predictive Control (MPC) and simulate an IEEE 13 bus network either copper plate or 3ph

Parameters:
  • self (EnergySystem object) – Object containing information on assets, market, network and time resolution.
  • ems_type (string) – Identifies whether the system is copper plate or 3ph. Default 3ph
  • i_unconstrained_lines (list) – List of network lines which have unconstrained current
  • v_unconstrained_buses (list) – List of buses at which the voltage is not constrained
Returns:

Output

PF_network_res : Network power flow results stored as a list of

objects

P_ES_ems : Charge/discharge power for storage assets at energy

management time resolution (kW)

P_import_ems :Power imported from central grid at energy

management time resolution (kW)

P_export_ems :Power exported to central grid at energy

management time resolution(kW)

P_demand_ems :System power demand at energy management time

resolution (kW)

Return type:

dictionary

Markets

OPEN Markets module

A Market class defines an upstream market which the EnergySystem is connected to. Attributes include the network location, prices of imports and exports over the simulation time-series, the demand charge paid on the maximum demand over the simulation time-series and import and export power limits.

The market class has a method which calculates the total revenue associated with a particular set of real and reactive power profiles over the simulation time-series.

class System.Markets.Market(bus_id, prices_export, prices_import, demand_charge, Pmax, Pmin, dt_market, T_market, FR_window=None, FR_capacity=None, FR_SOC_max=0.6, FR_SOC_min=0.4, FR_price=0.005, stochastic_date=None, daily_connection_charge=0.13)

A market class to handle prices and other market associated parameters.

Parameters:
  • bus_id (int) – id number of the bus in the network
  • prices_export (numpy.ndarray) – price paid for exports (£/kWh)
  • prices_import (numpy.ndarray) – price charged for imports (£/kWh)
  • demand_charge (float) – charge for the maximum demand over the time series (£/kWh)
  • Pmax (float) – maximum import power over the time series (kW)
  • Pmin (float) – minimum import over the time series (kW)
  • dt_market (float) – time interval duration (minutes)
  • T_market (int) – number of time intervals
  • FR_window (int) – binary value over time series to indicate when frequency response has been offered (0,1)
  • FR_capacity (float) – capacity of frequency response offered (kW)
  • FR_SOC_max (float) – max SOC at which frequency response can still be fulfilled if needed
  • FR_SOC_min (float) – min SOC at which frequency response can still be fulfilled if needed
  • FR_price (float) – price per kW capacity per hour avaiable (£/kW.h)
Returns:

Return type:

Market

calculate_revenue(P_import_tot, dt)

Calculate revenue according to simulation results

Parameters:
  • P_import_tot (float) – Total import power to the site over the time series (kW)
  • dt (float) – simulation time interval duration (minutes)
  • c_deg_lin (float) – cost of battery degradation associated with each kWh throughput (£/kWh)
Returns:

revenue – Total revenue generated during simulation

Return type:

float

Networks

OPEN 3 phase networks module

OPEN offers two options for network modelling. For balanced power flow analysis, the PandapowerNet class from the open-source python package pandapower can be used. For unbalanced multi-phase power flow analysis, OPEN offers the Network_3ph class.

class System.Network_3ph_pf.Network_3ph

A 3-phase electric power network. Default to an unloaded IEEE 13 Bus Test Feeder.

Parameters:
  • bus_df (pandas.DataFrame) – bus information, columns: [‘name’,’number’,’load_type’,’connect’, ‘Pa’,’Pb’,’Pc’,’Qa’,’Qb’,’Qc’], load_type: ‘S’ (slack),’PQ’,’Z’ or ‘I’ (only S and PQ are currently implemented), connect: ‘Y’ (wye) or ‘D’ (delta), ‘Px’ in (kW), ‘Qx’ in (kVAr)
  • capacitor_df (pandas.DataFrame) – capacitor information, columns [‘name’,’number’,’bus’,’kVln’, ‘connect’,’Qa’,’Qb’,’Qc’], connect: ‘Y’ (wye) or ‘D’ (delta), ‘kVln’: line-to-line base voltage, ‘Qx’ in (kVAr)
  • di_iter (np.ndarray) – change in the sum of abs phase currents at each Z-Bus iteration
  • dv_iter (np.ndarray) – change in the sum of abs phsae voltages at each Z-Bus iteration
  • i_abs_max (numpy.ndarray) – max abs line phase currents [line, phase] (|A|)
  • i_PQ_iter (numpy.ndarray) – current injected at each phase at each Z-Bus iteration [iter,phase] (A)
  • i_PQ_res (numpy.ndarray) – power flow result, current injected at each phase (excl. slack) (A)
  • i_net_res (numpy.ndarray) – power flow result, current injected at each phase (A)
  • i_slack_res (numpy.ndarray) – power flow result, current injected at slack bus phases (A)
  • Jabs_dPQdel_list (list of numpy.ndarray) – linear line abs current model, [P_delta,Q_delta] coeff. matrix list
  • Jabs_dPQwye_list (list of numpy.ndarray) – linear line abs current model, [P_wye,Q_wye] coeff. matrix list
  • Jabs_I0_list (list of numpy.ndarray) – linear line abs current model, constant vector list
  • J_dPQdel_list (list of numpy.ndarray) – linear line current model, [P_delta,Q_delta] coeff. matrix list
  • J_dPQwye_list (list of numpy.ndarray) – linear line current model, [P_wye,Q_wye] coeff. matrix list
  • J_I0_list (list of numpy.ndarray) – linear line current model, constant vector list
  • K_del (numpy.ndarray) – linear abs voltage model, [P_delta,Q_delta] coeff. matrix
  • K_wye (numpy.ndarray) – linear abs voltage model, [P_wye,Q_wye] coeff. matrix
  • K0 (numpy.ndarray) – linear abs voltage model, constant vector
  • line_config_df (pandas.DataFrame) – information on line configurations, columns: [‘name’,’Zaa’, ‘Zbb’,’Zcc’,’Zab’,’Zac’,’Zbc’,’Baa’,’Bbb’,’Bcc’,’Bab’,’Bac’,’Bbc’], ‘Zxx’ in (Ohms/length unit), ‘Bxx’ in (S/length unit) [base voltage of Vslack]
  • line_df (pandas.DataFrame) – line information: [‘busA’,’busB’,’Zaa’,’Zbb’,’Zcc’,’Zab’,’Zac’,’Zbc’, ‘Baa’,’Bbb’,’Bcc’,’Bab’,’Bac’,’Bbc’], ‘Zxx’ in (Ohms) ‘Bxx’ in (S) [base voltage of Vslack]
  • line_info_df – matches lines to their configurations: [‘busA’,’busB’,’config’, ‘length’,’Z_conv_factor’,’B_conv_factor’], Z,B_conv_factors used to match ‘lenth’ units to line_config_df ‘Zxx’ and ‘Bxx’ values
  • list_Yseries (list of numpy.ndarray) – list of series admittance matrices for the lines
  • list_Yshunt (list of numpy.ndarray) – list of shunt admittance matrices for the lines
  • M_del (numpy.ndarray) – linear voltage model, [P_delta,Q_delta] coeff. matrix
  • M_wye (numpy.ndarray) – linear voltage model, [P_wye,Q_wye] coeff. matrix
  • M0 (numpy.ndarray) – linear abs voltage model, constant vector
  • N_buses (int) – number of buses
  • N_capacitors (int) – number of capacitors
  • N_iter (int) – number of Z-Bus power flow solver iterations
  • N_phases (int) – number of phases
  • N_lines (int) – number of lines
  • N_transformers (int) – number of transformers
  • res_bus_df (pandas.DataFrame) – power flow result, bus information, columns: [‘name’,’number’, ‘load_type’,’connect’,’Sa’,’Sb’,’Sc’,’Va’,’Vb’,’Vc’,’Ia’,’Ib’,’Ic’] load_type: ‘S’ (slack),’PQ’,’Z’ or ‘I’ (only S and PQ are currently implemented), connect: ‘Y’ (wye) or ‘D’ (delta), ‘Sx’ in (kVA), ‘Vx’ in (V), ‘Ix’ in (A)
  • res_lines_df (pandas.DataFrame) – power flow result, line information, columns: [‘busA’,’busB’,’Sa’,’Sb’, ‘Sc’,’Ia’,’Ib’,’Ic’,’VAa’,’VAb’,’VAc’,’VBa’,’VBb’,’VBc’], ‘Sx’ in (VA), ‘Ix’ in (A), bus A voltages ‘VAx’ in (V), bus B voltages ‘VBx’ in (V).
  • S_del_lin0 (numpy.ndarray) – linear model, delta apparent power load (kVA)
  • S_PQloads_del_res (numpy.ndarray) – power flow result, delta apparent power load (kVA)
  • S_PQloads_wye_res (numpy.ndarray) – power flow result, wye apparent power load (kVA)
  • S_net_res (pandas.DataFrame) – power flow result, apparent power load at each phase (VA)
  • S_wye_lin0 – linear model, delta apparent power load (kVA) Y :
  • transformer_df (pandas.DataFrame) – transformer information, columns: [‘busA’,’busB’,’typeA’,’typeB’, ‘Zseries’,’Zshunt’], typex: ‘wye-g’, ‘wye’ or ‘delta’
  • v_abs_min (numpy.ndarray) – min abs bus voltages [bus, phase] (|V|)
  • v_abs_max (numpy.ndarray) – max abs bus voltages [bus, phase] (|V|)
  • v_iter (numpy.ndarray) – bus phase voltages at each Z-Bus iteration [iteration, phase]
  • v_lin_abs_res (numpy.ndarray) – linear model result, bus phase abs voltage (excl. slack) (|V|)
  • v_lin_res (numpy.ndarray) – linear model result, bus phase voltage (excl. slack) (V)
  • v_net_lin_abs_res (numpy.ndarray) – linear model result, bus phase abs voltage (|V|)
  • v_net_lin_res (numpy.ndarray) – linear model result, bus phase voltage (V)
  • v_net_lin0 (numpy.ndarray) – linear model, nominal bus phase voltages (V)
  • v_net_res (numpy.ndarray) – power flow result, bus phase voltages (V)
  • vs (numpy.ndarray) – slack bus phase voltages (V)
  • Vslack (float) – slack bus line-to-line voltage magnitude (|V|)
  • Vslack_ph (float) – slack bus line-to-phase voltage magnitude (|V|)
  • v_res (numpy.ndarray) – power flow result, bus phase voltages (excl. slack) (V)
  • Y (numpy.ndarray) – admittance matrix (excl. slack) (S)
  • Ynet (numpy.ndarray) – admittance matrix (S)
  • Y_non_singular – admittance matrix with 1e-20*I added (excl. slack) (S) [base voltage of Vslack]
  • Yns (numpy.ndarray) – admittance matrix partition [Yss, Ysn; Yns, Y] (S) [base voltage of Vslack] voltage of Vslack
  • Ysn (numpy.ndarray) – admittance matrix partition [Yss, Ysn; Yns, Y] (S) [base voltage of Vslack]
  • Yss (numpy.ndarray) – admittance matrix partition [Yss, Ysn; Yns, Y] (S) [base voltage of Vslack]
  • Z – impedance matrix (Ohm) [base voltage of Vslack]
  • Znet – impedance matrix (excl. slack) (Ohm) [base voltage of Vslack]
Returns:

Return type:

Network_3ph

clear_loads()

Removes all real and reactive power loads from the network by clearing bus_df.

linear_model_setup(v_net_lin0, S_wye_lin0, S_del_lin0)

Set up a linear model based on A. Bernstein, et al., “Load Flow in Multiphase Distribution Networks: Existence, Uniqueness, Non-Singularity and Linear Models,” IEEE Transactions on Power Systems, 2018.

Parameters:
  • v_net_lin0 (numpy.ndarray) – nominal operating point, bus phase voltages (V)
  • S_wye_lin0 (numpy.ndarray) – nominal operating point, apparent wye power loads (kVA)
  • S_del_lin0 (numpy.ndarray) – nominal operating point, apparent delta power loads (kVA)
linear_pf()

Solves the linear model based on A. Bernstein, et al., “Load Flow in Multiphase Distribution Networks: Existence, Uniqueness, Non-Singularity and Linear Models,” IEEE Transactions on Power Systems, 2018. First run linear_model_setup().

set_load(bus_id, ph_i, Pph, Qph)

Sets the P and Q load on a particular bus and phase

Parameters:
  • bus_id (int) – the load bus id
  • ph_i (int) – the load phase (either 0, 1 or 2)
  • Pph (float) – nominal operating point, apparent wye load (kVA)
  • Qph (float) – nominal operating point, apparent delta load (kVA)
set_pf_limits(v_abs_min_val, v_abs_max_val, i_abs_max_val)

Sets the abs bus phase voltage limits and abs line phase current limits

Parameters:
  • v_abs_min_val (float) – minimum abs voltage bus phase voltage limit
  • v_abs_max_val (float) – maximum abs voltage bus phase voltage limit
  • i_abs_max_val (float) – maximum abs line phase current limit
setup_network_ieee13()

Set up the network as the unloaded IEEE 13 Bus Test Feeder

update_YandZ()

Update the network admittance and impedance matrices

update_line_pf_results()

Updates the line power flow results dataframe res_lines_df, based on the results of zbus_pf().

v_flat()

Get the vector of 1 p.u. balanced bus phase voltages

Returns:
Return type:numpy.ndarray
zbus_pf()